Honeywell 393691 Installation Instructions Manual

Honeywell 393691 Installation Instructions Manual

Lp gas and natural gas conversion kits for vr8200/vr8300/sv9500/sv9600 family of combination gas controls

Advertisement

Available languages

Available languages

Quick Links

393691 LP Gas and 394588
Natural Gas Conversion Kits
FOR VR8200/VR8300/SV9500/SV9600 FAMILY OF
COMBINATION GAS CONTROLS

APPLICATION

The 393691 LP Conversion Kit changes
VR8200/VR8300/SV9500/SV9600 family
combination gas controls from regulated natural gas
to regulated LP gas. The 394588 Natural Gas
Conversion Kit changes
VR8200/VR8300/SV9500/SV9600 family
combination gas controls from regulated LP gas to
regulated natural gas. Kits include a new cap screw,
pressure regulator adjustment screw, spring and
conversion label.
To use this kit, assure gas control is equipped with a
standard or slow opening pressure regulator.
NOTE: Step regulator valves cannot be converted.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to
follow instructions can damage product or
cause a hazardous condition.
2. Check ratings given in instructions and on
product to make sure product is suitable for
your application.
3. The installer must be a trained, experienced
service technician.
4. After installation is complete, use these instruc-
tions to check out product operation.
INSTALLATION INSTRUCTIONS
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property
damage.
Follow these warnings exactly:
1. Disconnect power supply before wiring to
prevent electrical shock or equipment
damage.
2. To avoid dangerous accumulation of fuel
gas, turn off gas supply at appliance service
valve before starting installation and
Perform Gas Leak Test after completion of
installation.
3. Use only your hand to turn gas control knob.
Never use any tools. If gas control knob will
not operate by hand, then a qualified
technician should replace the gas control.
Force or attempted repair may result in fire
or explosion.
4. Change main and pilot burner orifices to
meet appliance manufacturer
specifications.

To convert from one gas to another:

1. Turn off gas supply at the appliance service
valve.
2. Remove regulator cap screw and pressure
regulator adjusting screw. Refer to Fig. 1.
3. Remove the existing spring.
4. Insert the replacement spring. Refer to Fig. 2.
PRESSURE REGULATOR
ADJUSTMENT
(UNDER CAP SCREW)
INLET
PRESSURE TAP
INLET
1
THERMOCOUPLE
CONNECTION
1
RED
RESET
BUTTON
1
THERMOCOUPLE CONNECTION AND RED RESET BUTTON
ON STANDING PILOT MODELS ONLY.
Fig. 1. Top view of VR8200 combination gas control.
CONVENIENCE
WIRING
TERMINALS (2)
TERMINALS (2)
(OPTIONAL)
OUTLET
PRESSURE
TAP
OUTLET
PILOT OUTLET
PILOT ADJUSTMENT
GAS
(UNDER CAP SCREW)
CONTROL
KNOB
69-0244EF-01
M8084

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell 393691

  • Page 1: Installation Instructions

    FOR VR8200/VR8300/SV9500/SV9600 FAMILY OF COMBINATION GAS CONTROLS INSTALLATION INSTRUCTIONS APPLICATION WARNING Fire or Explosion Hazard. The 393691 LP Conversion Kit changes Can cause severe injury, death or property VR8200/VR8300/SV9500/SV9600 family damage. combination gas controls from regulated natural gas Follow these warnings exactly: to regulated LP gas.
  • Page 2 Smell for gas around the appliance near the 10.0 in. wc (2.5 kPa) for LP gas regulator floor. Do not relight pilot flame if you smell gas. (393691) and 3.5 in. wc (0.9 kPa) for natural gas 2. Turn gas control knob counterclockwise regulator (394588).
  • Page 3 393691 LP GAS AND 394588 NATURAL GAS CONVERSION KITS 5. Light main burner and read pressure gauge. 6. If necessary, adjust pressure regulator to match PROPER FLAME appliance rating. (On step-opening regulators, ADJUSTMENT match the full rate outlet pressure.) 3/8 TO 1/2 IN.
  • Page 4 393691 LP GAS AND 394588 NATURAL GAS CONVERSION KITS 8. Turn gas supply back on to other appliances Time (sec) Flow (cfh) Flow (m /hr) and relight all pilot flames according to 1.30 appliance manufacturer instructions. 9. Proceed to Checkout section.
  • Page 5 DE COMBINAISONS VR8200/VR8300/SV9500/SV9600 INSTRUCTIONS D’INSTALLATION APPLICATION AVERTISSEMENT La trousse de conversion 393691 pour le gaz de Risque d’incendie ou d’explosion. Peut causer des blessures graves, le décès pétrole liquéfié fait passer les appareils de contrôle du gaz de la famille de combinaisons ou des dommages matériels.
  • Page 6 TROUSSES DE CONVERSION 393691 POUR LE GAZ DE PÉTROLE LIQUÉFIÉ ET 394588 POUR LE GAZ NATUREL Effectuer un test de fuite de gaz CODE COULEUR POUR NATUREL AVERTISSEMENT NOIR ARGENT D'OBTURATION JOINT TORIQUE NOIR NOIR Risque d’incendie ou d’explosion. Peut causer des blessures graves, le décès ou VIS DE RÉGLAGE DU...
  • Page 7 TROUSSES DE CONVERSION 393691 POUR LE GAZ DE PÉTROLE LIQUÉFIÉ ET 394588 POUR LE GAZ NATUREL Ajuster la flamme de la veilleuse Vérification de la pression du gaz à l’aide d’un manomètre La flamme de la veilleuse devrait envelopper 10 à...
  • Page 8 TROUSSES DE CONVERSION 393691 POUR LE GAZ DE PÉTROLE LIQUÉFIÉ ET 394588 POUR LE GAZ NATUREL a. Pour les cadrans de compteur de gaz à un Temps (s) Débit (pi Débit (m par rotation, utilisez directement le 1,78 Tableau 1.

This manual is also suitable for:

394588

Table of Contents