INSTALLATION AND MAINTENANCE INSTRUCTIONS
Velociti
Series
®
AMM-4SF Interface Module
SPECIFICATIONS
Normal Operating Voltage:
Maximum Current Draw:
Average Operating Current:
EOL Resistance:
Maximum IDC Wiring Resistance:
IDC Supply Voltage (between Terminals T10 and T11)
Regulated DC Voltage:
Ripple Voltage:
Alarm Current:
Standby Current:
Temperature Range:
Humidity:
Dimensions:
Accessories:
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The AMM-4SF Interface Module is intended for use in intelligent, two-wire
systems, where the individual address of each module is selected using the
built-in rotary switches. This module allows intelligent panels to interface and
monitor two-wire conventional smoke detectors. It transmits the status (nor-
mal, open, or alarm) of one full zone of conventional detectors back to the
control panel. All two-wire detectors being monitored must be UL compatible
with this module. AMM-4SF is capable of handling more than one detector in
alarm condition.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Gamewell-FCI system control panel only (list available from Gamewell-FCI).
Please refer to Gamewell-FCI's document #9000-0427 for full list of compat-
ible devices.
FIGURE 1. CONTROLS AND INDICATORS
15 to 32 VDC
5.1 mA (LED on)
255 µA (LED flashing - in Velociti mode); 230 µA (LED flashing - in CLIP mode)
3.9K Ohms
25 Ohms
24 VDC power limited
0.1 Volts RMS maximum
90 mA per module
13 mA Maximum @24 VDC
32˚F to 120˚F (0˚C to 49˚C)
10% to 93% Non-condensing
4.5˝ H × 4 W × 1.25˝ D (Mounts to a 4˝ square by 2.125˝ deep box.)
SMB500 Electrical Box
C1059-00
MOUNTING
The AMM-4SF mounts directly to 4-inch square electrical boxes. (See Figure 2.)
The box must have a minimum depth of 2.125 inches. Surface mounted elec-
trical boxes (SMB500) are available from Gamewell-FCI.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. This module is intended for power-limited wiring only.
1.
Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2.
Set the address on the module per job drawings.
3.
Secure module to electrical box supplied by installer. (See Figure 2.)
FIGURE 2. MODULE MOUNTING
1
12 Clintonville Road
Northford, CT 06472-1653
Phone: 203.484.7161; Fax: 203.484.7118
www.gamewell-fci.com
ISOLATED
QUADRANT
C1066-00
I56-3552-006
7/1/2022